House Wire FR-LSH

Suitable for use in conduit and for fixed, protected installation particularly suitable for wiring in fire and explosion prone areas, chemical factories, densely wired areas, public buildings, schools, hospitals, commercial complexes, theatres, etc.
Technical Data
  •   Approvals : IS 694 marked, FIA/TAC
  •   Voltage Grade: Up to and including 1100V
  •   Conductor : Thin strands of electrolytic copper are multi-drawn for uniformity of resistance, dimension and flexibility.
  •   Insulation : Specially formulated flame retardant low smoke low halogen compound to restrict the spread of flames in fire situation. The smoke emitted by the burning cable is considerably low compared to traditional cables. This ensures improved visibility for evacuation of trapped victims and facilitates fire fighting operation.
  •   Insulation Conformity: IS 5831 Type A/D FR-LSH 70°C
  •   Colours : Entire cable has white base and a double strip of Green, Black, Red, Yellow, Blue, Grey, running along the cable length
  •   Packing : 90 mtr. coils packed in protective cartons. Project coils of 180 mtr. also available.
Cable Design Parameters
Kindly complete the part numbers forthese cables by adding the suffix (in place of rxx') for the colour required:
01 - Green, 02 - Black, 03 - Red, O4- Blue, 05- Yellow, 06 - Grey.
Part Number Nominal Cross Sectional Area (Sq. mm) Nominal Insulation Thickness (mm) Number *Nominal Dia. of Strands Approx. Overall Diameter (mm) Max. DC Conductor Resistance at 20oC (Km) Current Rating (Amps)
Casing Concealed
01020101xx50 1 0.7 14/0.3 2.7 18.1 14 13
01020102xx50 1.5 0.7 22/0.3 3.0 12.1 18 16
01020103xx50 2.5 0.8 36/0.3 3.7 7.41 24 20
01020104xx50 4** 0.8 56/0.3 4.1 4.95 30 26
Properties

Test Test Method Values
Limited Oxygen Index IS 10810 P - 58 >29%
Limited Temperature Index IS 10810 P - 64 >250°C
Smoke Density (Light Absorption) IS 13360 P - 6/Sec 9 < 60%
Acid Gas Generation IS 10810 P - 59 <20%